Interactive test drive · PSC-1

Watch PSC-1 turn an AI rack into a smooth load.

An NVL72-class training rack swings by tens of kilowatts every couple of seconds. NVIDIA's GB300 racks already smooth this with power-supply capacitors, a power floor and a ramp cap, cutting peak grid demand by up to 30%. The floor works by burning energy. PSC-1 stores it instead. Run the two-minute test (it plays in 30 seconds) to compare the three.

Join the pilot
Rack demand–
Grid draw–
Shelf charge–
Burned as heat–
Free run · training in progress–

One rack, last 30 s

GPU demandGrid draw

What the utility sees: 500 racks

No smoothingGPU-levelPSC-1

Test setup

Changes apply live
Shape of the GPU power swings.
500 racks
≈ 60 MW of IT load
2.5 kW/s
= 1.3 MW/s for the cluster
$0.08/kWh
Used for the yearly cost figures.
Fire an event
THE PROBLEM

Training racks pulse

When thousands of GPUs pause together to exchange results, rack power drops by most of its GPU share within milliseconds, then comes straight back. Across a hall, that's tens of megawatts every few seconds.

TODAY'S FIX

Smooth it at the GPU

NVIDIA's GB300 racks store about 65 J per GPU in the power-supply capacitors, roughly 4.7 kJ per 72-GPU rack. That's under a tenth of a second of an 80 kW swing. A ramp cap slows the surge, and a power floor keeps the GPUs drawing through each pause. NVIDIA reports up to 30% lower peak grid demand. The floor's energy becomes heat.

PSC-1

Store what the floor burns

A 2U shelf on the rack busbar holds 100 kJ, more than 20× the rack's power-supply capacitance. It soaks up each dip and gives the energy back on the next surge, so the utility sees a slow, steady load. GPU-level smoothing stays on as a backstop for job starts and stops.

Want to see it on your racks?

Makers: design PSC-1 into your power shelf. Developers: join the pilot.